Cabling requirements for G0 Target Controls system DRAFT 25-apr-2000 I. Target --> Controls racks Summary: 1) Vacuum system cables ?? 2) Temperature sensors 12 9-conductor shielded cable with D-connectors (temp sensors) 3) tachometer 1 BNC cable (carrying TTL pulse train) 4) JT valves ?? 5) Target position readback 8 two-conductor cables for 4 position control (24V) lines 8 two-conductor cables for hard-stop (microswitch) indicators 6) Heaters 2 two-conductor low-resistance, power cables for HP heater (25A,40A) 2 two conductor low-resistance, power cables for LP heater (80W max) 7) Motor control 1 power cable (120V, 0.5 Amps) 8) Miscellaneous for vacuum/beam interlocks about 12 RG58/U-type BNC cables, carry 24 V max. II. Gas Panel --> Controls racks Summary: 1) Pressure Transducers 40 Twin-axial BNC cables (Analog input) 2) General control 10 RG58/BNC cables for (Analog output) 3) Valve readback 30 twisted pair 16-pin ribbon cable (digital input: valves) 4) Valve control ?? III. Target --> Hall C counting house (not G0 CH) Summary: 1 shielded 8-conductor, 1" MS connectors 2 shielded 16-conductor, connectors unspecified 4 RG58 w/ BNC connectors 1) HP heater manual override: 1 cable (shielded 8 conductor) signals will carry DC volts 0-10V. connectors are MS, 1" diam, provided by UMd 2) ethernet for VME crate (crate in hall) 3) Interlock and emergency valve control: 2 cables, 16 conductor, shielded, low DC voltage connectors unspecified. 4) motor controller/tachometer: no cables required (motor controller will reside in hall) (tachometer read via RS232 downstairs) 5) target position control: 4 RG58 cables (position readback)